SectionsSupply-and-extract air handling units
Back to section: Supply and extract

Supply-and-extract air handling units

Two air paths provide coordinated supply and extraction. Their balance, separation and control are selected together; heat recovery is an additional function.

Principle and scope

A supply-and-extract unit combines two air paths in one coordinated assembly. The flows are selected to meet ventilation and room-pressure requirements; equal nominal flows do not by themselves establish a balanced building.

The assembly may include heat recovery, but having two fans does not prove that it does. Check air-path separation, intake and discharge positions, leakage, control interaction and access to both sides.

Balance and control

Specify both airflows at their own external pressure, including normal, reduced and boost modes. Pressure relationships may deliberately require unequal flows. Allow for other extract systems and leakage through the building. Commission both paths together; a common speed signal does not guarantee a stable flow ratio when filters load differently.

Calculate one air stream at a time. This calculation does not balance supply and extract or match both air paths.

Calculate sensible air load

Sensible air load calculation

Calculate the heat rate associated with a specified temperature change in one air stream. Enter all five values for your stated operating conditions.

Mass flow ṁ = ρ × V̇ / 3600; temperature change ΔT = Tout − Tin; sensible heat rate Q̇ = ṁ × cp × ΔT. With the units below, the result is in kW. Positive Q̇ means heating; negative Q̇ means cooling. Zero flow or zero temperature difference gives zero sensible load.

For a steady, single-phase air stream with constant user-supplied properties. The balance excludes latent heat, moisture changes, phase change, shaft work and kinetic/potential energy changes. It does not select a fan, coil or complete AHU.

Topic for the local draft

Opening a page does not select anything. A topic choice records context only; no product or configuration is selected.

Operating inputs

Use density at the same state and volume basis as the entered airflow. Enter cp in kJ/(kg·K), not J/(kg·K). Density and cp are editable assumptions; no universal values are prefilled. Check that your temperatures and properties describe gas-phase air. This tool does not check phase boundaries or property-table consistency.

Interactive calculation requires JavaScript. The formula, units, scope and reference information remain available here for manual use.

Heat recovery

In a combined supply-and-extract unit, recovery uses the two available paths. Select the exchanger and fan pressure duties together. During frost or bypass modes, check what happens to room ventilation and pressure; a recovery controller must not silently defeat the specified airflow regime.

Commissioning and service

Measure both sides during commissioning and after filter or control changes. Check frost and fault modes for their effect on building pressure. Maintenance records should distinguish supply and extract filters, fan settings and sensor locations so readings cannot be attributed to the wrong path.

Differential-pressure sensor

The sensor provides a differential-pressure signal for the selected control scheme. The result depends on the pressure points and measurement range.

One differential-pressure sensor with two pressure connections on white.
Back to section: Supply and extract

A guide to equipment and selection; the final configuration and performance require project-specific confirmation.