Model
OBAIR FG10 Cabinet Fan Coil Unit
OBAIR FG10 is a catalogue-listed cabinet fan coil unit with 26 published technical parameters. Selection requires confirmation of project conditions.
When to consider this equipment
Use this category when air must be heated or cooled close to the occupied zone. Final capacity, water temperatures, noise and installation arrangement must be checked for the project.
What to include in an enquiry
Provide room duty, entering and leaving water temperatures, airflow or acoustic limits, mounting arrangement and available service space.
Verified technical data
FG10
- Standard airflow - return-air condition
- 10.5 1000 m³/h
- Airflow range - return-air condition
- 10.5–13.2 1000 m³/h
- Type C rated cooling capacity - return-air condition
- 75 kW
- Type C rated heating capacity - return-air condition
- 129.7 kW
- Type C water flow rate - return-air condition
- 12.9 m3/h
- Type C water resistance - return-air condition
- 51 kPa
- Type C pipe diameter - return-air condition
- 40*2 DN
- Type D rated cooling capacity - return-air condition
- 95 kW
- Type D rated heating capacity - return-air condition
- 156.1 kW
- Type D water flow rate - return-air condition
- 16.3 m3/h
- Type D water resistance - return-air condition
- 52 kPa
- Type D pipe diameter - return-air condition
- 50*2 DN
- Standard airflow - fresh-air condition
- 10.5 1000 m³/h
- Airflow range - fresh-air condition
- 10.5–13.2 1000 m³/h
- Type C rated cooling capacity - fresh-air condition
- 160.7 kW
- Type C rated heating capacity - fresh-air condition
- 167.4 kW
- Type C water flow rate - fresh-air condition
- 27.6 m3/h
- Type C water resistance - fresh-air condition
- 58.7 kPa
- Type C pipe diameter - fresh-air condition
- 65*2 DN
- Type D rated cooling capacity - fresh-air condition
- 199.9 kW
- Type D rated heating capacity - fresh-air condition
- 207.9 kW
- Type D water flow rate - fresh-air condition
- 34.4 m3/h
- Type D water resistance - fresh-air condition
- 59.8 kPa
- Type D pipe diameter - fresh-air condition
- 65*2 DN
- Compatible motor by static pressure - Type C
- {"160":2.2,"200":3,"240":3,"280":3,"320":3,"360":3,"400":3} kW by external static pressure in Pa
- Compatible motor by static pressure - Type D
- {"160":3,"200":3,"240":3,"280":3,"320":3,"360":3,"400":3} kW by external static pressure in Pa
On request
3D model not yet available
Selection from project conditions is available on enquiry