Model

OBAIR FG2.5 Cabinet Fan Coil Unit

OBAIR FG2.5 Cabinet Fan Coil Unit is listed in the OBAIR catalogue. Standard airflow - return-air condition: 2.5 1000 m³/h; Airflow range - return-air condition: 2.1–3.2 1000 m³/h. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category when air must be heated or cooled close to the occupied zone. Final capacity, water temperatures, noise and installation arrangement must be checked for the project.

What to include in an enquiry

Provide room duty, entering and leaving water temperatures, airflow or acoustic limits, mounting arrangement and available service space.

Verified technical data

FG2.5

Standard airflow - return-air condition
2.5 1000 m³/h
Airflow range - return-air condition
2.1–3.2 1000 m³/h
Type C rated cooling capacity - return-air condition
18.2 kW
Type C rated heating capacity - return-air condition
32.8 kW
Type C water flow rate - return-air condition
3.1 m3/h
Type C water resistance - return-air condition
18 kPa
Type C pipe diameter - return-air condition
40*2 DN
Type D rated cooling capacity - return-air condition
22.9 kW
Type D rated heating capacity - return-air condition
37.7 kW
Type D water flow rate - return-air condition
3.9 m3/h
Type D water resistance - return-air condition
38 kPa
Type D pipe diameter - return-air condition
40*2 DN
Standard airflow - fresh-air condition
2.5 1000 m³/h
Airflow range - fresh-air condition
2.1–3.2 1000 m³/h
Type C rated cooling capacity - fresh-air condition
38.1 kW
Type C rated heating capacity - fresh-air condition
39.7 kW
Type C water flow rate - fresh-air condition
6.5 m3/h
Type C water resistance - fresh-air condition
20.7 kPa
Type C pipe diameter - fresh-air condition
40*2 DN
Type D rated cooling capacity - fresh-air condition
50.3 kW
Type D rated heating capacity - fresh-air condition
52.3 kW
Type D water flow rate - fresh-air condition
8.7 m3/h
Type D water resistance - fresh-air condition
43.7 kPa
Type D pipe diameter - fresh-air condition
40*2 DN
Compatible motor by static pressure - Type C
{"120":0.37,"160":0.37,"200":0.45,"240":0.45} kW by external static pressure in Pa
Compatible motor by static pressure - Type D
{"120":0.37,"160":0.45,"200":0.45,"240":0.45} kW by external static pressure in Pa
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry