Model

OBAIR FP-238 Fan Coil Unit

OBAIR FP-238 Fan Coil Unit is listed in the OBAIR catalogue. Rated airflow - high speed: 2380 m3/h; Rated airflow - medium speed: 1975 m3/h. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category when air must be heated or cooled close to the occupied zone. Final capacity, water temperatures, noise and installation arrangement must be checked for the project.

What to include in an enquiry

Provide room duty, entering and leaving water temperatures, airflow or acoustic limits, mounting arrangement and available service space.

Verified technical data

FP-238

Rated airflow - high speed
2380 m3/h
Rated airflow - medium speed
1975 m3/h
Rated airflow - low speed
1255 m3/h
Cooling capacity - high speed
14370 W
Cooling capacity - medium speed
11600 W
Cooling capacity - low speed
9200 W
Heating capacity - high speed
20600 W
Fan quantity
4 count
Motor quantity
2 count
High-speed input power at 12 Pa
221 W
High-speed input power at 30 Pa
245 W
High-speed input power at 50 Pa
285 W
Water mass flow rate
2472 kg/h
Water resistance
48 kPa
FCEER at 12 Pa
54
FCEER at 30 Pa
50
FCEER at 50 Pa
44
FCCOP at 12 Pa
73
FCCOP at 30 Pa
67
FCCOP at 50 Pa
59
High-speed noise at 12 Pa
51.0 dB(A)
High-speed noise at 30 Pa
52.0 dB(A)
High-speed noise at 50 Pa
53.0 dB(A)
Fan type
Front-curved Multi-blade Galvanized Steel Plate Centrifugal Double-suction Fan
Motor type
Single-phase Capacitor Run Motor
Motor insulation class
B
Power supply
220V/~/50Hz
Heat-exchanger construction
Copper tubes with high-efficiency flanged aluminum fins, tightly expanded into a single unit
Heat-exchanger working pressure
1.6 MPa
Inlet and outlet pipe
R1 3/4 (Conical Internal Thread)
Condensate pipe
R1 3/4 (Conical External Thread)
Medium-speed cooling total-heat correction factor
0.9 factor
Medium-speed cooling sensible-heat correction factor
0.85 factor
Low-speed cooling total-heat correction factor
0.66 factor
Low-speed cooling sensible-heat correction factor
0.61 factor
Medium-speed heating total-heat correction factor
0.85 factor
Medium-speed heating sensible-heat correction factor
0.62 factor
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry