Model

OBAIR FP-51 Fan Coil Unit

OBAIR FP-51 Fan Coil Unit is listed in the OBAIR catalogue. Rated airflow - high speed: 510 m3/h; Rated airflow - medium speed: 380 m3/h. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category when air must be heated or cooled close to the occupied zone. Final capacity, water temperatures, noise and installation arrangement must be checked for the project.

What to include in an enquiry

Provide room duty, entering and leaving water temperatures, airflow or acoustic limits, mounting arrangement and available service space.

Verified technical data

FP-51

Rated airflow - high speed
510 m3/h
Rated airflow - medium speed
380 m3/h
Rated airflow - low speed
280 m3/h
Cooling capacity - high speed
3600 W
Cooling capacity - medium speed
3160 W
Cooling capacity - low speed
2290 W
Heating capacity - high speed
5150 W
Fan quantity
2 count
Motor quantity
1 count
High-speed input power at 12 Pa
45 W
High-speed input power at 30 Pa
56 W
High-speed input power at 50 Pa
66 W
Water mass flow rate
618 kg/h
Water resistance
23 kPa
FCEER at 12 Pa
72
FCEER at 30 Pa
59
FCEER at 50 Pa
51
FCCOP at 12 Pa
98
FCCOP at 30 Pa
81
FCCOP at 50 Pa
70
High-speed noise at 12 Pa
38.0 dB(A)
High-speed noise at 30 Pa
40.5 dB(A)
High-speed noise at 50 Pa
43.0 dB(A)
Fan type
Front-curved Multi-blade Galvanized Steel Plate Centrifugal Double-suction Fan
Motor type
Single-phase Capacitor Run Motor
Motor insulation class
B
Power supply
220V/~/50Hz
Heat-exchanger construction
Copper tubes with high-efficiency flanged aluminum fins, tightly expanded into a single unit
Heat-exchanger working pressure
1.6 MPa
Inlet and outlet pipe
R1 3/4 (Conical Internal Thread)
Condensate pipe
R1 3/4 (Conical External Thread)
Medium-speed cooling total-heat correction factor
0.87 factor
Medium-speed cooling sensible-heat correction factor
0.84 factor
Low-speed cooling total-heat correction factor
0.72 factor
Low-speed cooling sensible-heat correction factor
0.68 factor
Medium-speed heating total-heat correction factor
0.83 factor
Medium-speed heating sensible-heat correction factor
0.66 factor
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry