OBAIR SF 200 — Water-cooled Unitary Air Conditioner (Vertical) R410A
OBAIR SF 200 is listed with nominal airflow 35,000 m³/h. No complete L × W × H envelope is claimed for this row.
When to consider this equipment
Use this category for ventilation or air-handling duties. The section sequence, filtration, heating, cooling, recovery and control functions must follow the project air states.
What to include in an enquiry
Provide supply and extract airflow, outdoor and indoor design conditions, external static pressure, filtration class, heating and cooling duties, dimensions and service constraints. The printed designation is not a complete factory order code and must not be used for ordering without confirmation.
Verified technical data
SF 200
- Model
- SF 200
- Cooling capacity
- 195.8 kW
- Electric heating capacity
- 60 kW
- Nominal airflow
- 35000 m3/h
- External static pressure
- 500 Pa
- Temperature-control range
- Summer 22-28℃±1℃, Winter 18-24℃±1℃
- Cooling-capacity adjustment range
- 0,20,40,60,80,100 %
- Compressor type
- Hermetic Scroll
- Indoor-unit power supply
- 380V/3N~/50Hz
- Fan power
- 11 kW
- Cooling input power
- 52.2 kW
- Water flow
- 44.9 m3/h
- Water pressure drop
- 40 kPa
- Inlet/outlet pipe diameter
- 80 DN
- Condensing-water pipe diameter
- 25 DN
- Indoor-unit weight
- 1700 kg
- Catalog drawing dimension A
- 1280 mm
- Catalog drawing dimension B
- 2700 mm
- Catalog drawing dimension C
- 2130 mm
- Catalog drawing dimension E
- 2616 mm
- Catalog drawing dimension F
- 1556 mm
- Catalog drawing dimension G
- 565 mm
- Catalog drawing dimension H
- 450 mm
- Catalog drawing dimension J
- 565 mm
- Return-air flange
- 2616*1556 mm
- Supply-air flange
- 565*565*2 mm
On request
3D model not yet available
Selection from project conditions is available on enquiry