OBAIR SF 100 — Constant Temperature and Humidity Water-cooled Unitary Air Conditioner (Vertical) R410A

OBAIR SF 100 is listed with nominal airflow 18,000 m³/h. No complete L × W × H envelope is claimed for this row.

When to consider this equipment

Use this category for ventilation or air-handling duties. The section sequence, filtration, heating, cooling, recovery and control functions must follow the project air states.

What to include in an enquiry

Provide supply and extract airflow, outdoor and indoor design conditions, external static pressure, filtration class, heating and cooling duties, dimensions and service constraints. The printed designation is not a complete factory order code and must not be used for ordering without confirmation.

Verified technical data

SF 100

Model
SF 100
Cooling capacity
100.8 kW
Electric heating capacity
45 kW
Nominal airflow
18000 m3/h
External static pressure
300 Pa
Temperature-control range
Summer 22-28℃±1℃, Winter 18-24℃±1℃
Humidity-control range
50-70%±5%
Cooling-capacity adjustment range
0,20,40,60,80,100 %
Humidification capacity
25 kg/h
Humidification power
18.75 kW
Compressor type
Hermetic Scroll
Indoor-unit power supply
380V/3N~/50Hz
Fan power
7.5 kW
Cooling input power
30.8 kW
Maximum input power
94.6 kW
Water flow
23.1 m3/h
Water pressure drop
35 kPa
Inlet/outlet pipe diameter
65 DN
Condensing-water pipe diameter
25 DN
Indoor-unit weight
900 kg
Catalog drawing dimension A
1200 mm
Catalog drawing dimension B
2100 mm
Catalog drawing dimension C
1850 mm
Catalog drawing dimension E
2016 mm
Catalog drawing dimension F
1236 mm
Catalog drawing dimension G
405 mm
Catalog drawing dimension H
315 mm
Catalog drawing dimension J
405 mm
Return-air flange
2016*1236 mm
Supply-air flange
405*405*2 mm
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry