Model

OBAIR SF 120 — Constant Temperature and Humidity Water-cooled Unitary Air Conditioner (Vertical) R410A

OBAIR SF 120 is listed with nominal airflow 21,000 m³/h. No complete L × W × H envelope is claimed for this row.

When to consider this equipment

Use this category for ventilation or air-handling duties. The section sequence, filtration, heating, cooling, recovery and control functions must follow the project air states.

What to include in an enquiry

Provide supply and extract airflow, outdoor and indoor design conditions, external static pressure, filtration class, heating and cooling duties, dimensions and service constraints. The printed designation is not a complete factory order code and must not be used for ordering without confirmation.

Verified technical data

SF 120

Model
SF 120
Cooling capacity
117.6 kW
Electric heating capacity
55 kW
Nominal airflow
21000 m3/h
External static pressure
400 Pa
Temperature-control range
Summer 22-28℃±1℃, Winter 18-24℃±1℃
Humidity-control range
50-70%±5%
Cooling-capacity adjustment range
0,33,66,100 %
Humidification capacity
30 kg/h
Humidification power
22.5 kW
Compressor type
Hermetic Scroll
Indoor-unit power supply
380V/3N~/50Hz
Fan power
11 kW
Cooling input power
36.4 kW
Maximum input power
114 kW
Water flow
26.9 m3/h
Water pressure drop
30 kPa
Inlet/outlet water-pipe diameter — performance table
65 DN
Condensing-water pipe diameter
25 DN
Indoor-unit weight
960 kg
Catalog drawing dimension A
1200 mm
Catalog drawing dimension B
2300 mm
Catalog drawing dimension C
1850 mm
Catalog drawing dimension E
2116 mm
Catalog drawing dimension F
1236 mm
Catalog drawing dimension G
455 mm
Catalog drawing dimension H
355 mm
Catalog drawing dimension J
455 mm
Inlet/outlet water-pipe diameter — dimensions table
80 DN
Return-air flange
2216*1236 mm
Supply-air flange
455*455*2 mm
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry