Model

OBAIR SF 200 — Constant Temperature and Humidity Water-cooled Unitary Air Conditioner (Vertical) R410A

OBAIR SF 200 is listed with nominal airflow 35,000 m³/h. No complete L × W × H envelope is claimed for this row.

When to consider this equipment

Use this category for ventilation or air-handling duties. The section sequence, filtration, heating, cooling, recovery and control functions must follow the project air states.

What to include in an enquiry

Provide supply and extract airflow, outdoor and indoor design conditions, external static pressure, filtration class, heating and cooling duties, dimensions and service constraints. The printed designation is not a complete factory order code and must not be used for ordering without confirmation.

Verified technical data

SF 200

Model
SF 200
Cooling capacity
195.8 kW
Electric heating capacity
80 kW
Nominal airflow
35000 m3/h
External static pressure
500 Pa
Temperature-control range
Summer 22-28℃±1℃, Winter 18-24℃±1℃
Humidity-control range
50-70%±5%
Cooling-capacity adjustment range
0,20,40,60,80,100 %
Humidification capacity
45 kg/h
Humidification power
35.2 kW
Compressor type
Hermetic Scroll
Indoor-unit power supply
380V/3N~/50Hz
Fan power
15 kW
Cooling input power
56.2 kW
Maximum input power
171.4 kW
Water flow
44.9 m3/h
Water pressure drop
40 kPa
Inlet/outlet pipe diameter
80 DN
Condensing-water pipe diameter
25 DN
Indoor-unit weight
1800 kg
Catalog drawing dimension A
1380 mm
Catalog drawing dimension B
2700 mm
Catalog drawing dimension C
2130 mm
Catalog drawing dimension E
2616 mm
Catalog drawing dimension F
1556 mm
Catalog drawing dimension G
565 mm
Catalog drawing dimension H
450 mm
Catalog drawing dimension J
565 mm
Return-air flange
2616*1556 mm
Supply-air flange
565*565*2 mm
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry