Model

OBAIR SF 50 — Constant Temperature and Humidity Water-cooled Unitary Air Conditioner (Vertical) R410A

OBAIR SF 50 is listed with nominal airflow 9,500 m³/h. No complete L × W × H envelope is claimed for this row.

When to consider this equipment

Use this category for ventilation or air-handling duties. The section sequence, filtration, heating, cooling, recovery and control functions must follow the project air states.

What to include in an enquiry

Provide supply and extract airflow, outdoor and indoor design conditions, external static pressure, filtration class, heating and cooling duties, dimensions and service constraints. The printed designation is not a complete factory order code and must not be used for ordering without confirmation.

Verified technical data

SF 50

Model
SF 50
Cooling capacity
49.2 kW
Electric heating capacity
25 kW
Nominal airflow
9500 m3/h
External static pressure
250 Pa
Temperature-control range
Summer 22-28℃±1℃, Winter 18-24℃±1℃
Humidity-control range
50-70%±5%
Cooling-capacity adjustment range
0,33,66,100 %
Humidification capacity
15 kg/h
Humidification power
11.6 kW
Compressor type
Hermetic Scroll
Indoor-unit power supply
380V/3N~/50Hz
Fan power
4 kW
Cooling input power
15.1 kW
Maximum input power
51.7 kW
Water flow
11.3 m3/h
Water pressure drop
30 kPa
Inlet/outlet pipe diameter
50 DN
Condensing-water pipe diameter
25 DN
Indoor-unit weight
600 kg
Catalog drawing dimension A
950 mm
Catalog drawing dimension B
1950 mm
Catalog drawing dimension C
1950 mm
Catalog drawing dimension E
1866 mm
Catalog drawing dimension F
646 mm
Catalog drawing dimension G
455 mm
Catalog drawing dimension H
-- mm
Catalog drawing dimension J
455 mm
Return-air flange
1866*646 mm
Supply-air flange
455*455 mm
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry