Model

OBAIR SF 80 — Constant Temperature and Humidity Water-cooled Unitary Air Conditioner (Vertical) R410A

OBAIR SF 80 is listed with nominal airflow 14,000 m³/h. No complete L × W × H envelope is claimed for this row.

When to consider this equipment

Use this category for ventilation or air-handling duties. The section sequence, filtration, heating, cooling, recovery and control functions must follow the project air states.

What to include in an enquiry

Provide supply and extract airflow, outdoor and indoor design conditions, external static pressure, filtration class, heating and cooling duties, dimensions and service constraints. The printed designation is not a complete factory order code and must not be used for ordering without confirmation.

Verified technical data

SF 80

Model
SF 80
Cooling capacity
77.2 kW
Electric heating capacity
35 kW
Nominal airflow
14000 m3/h
External static pressure
300 Pa
Temperature-control range
Summer 22-28℃±1℃, Winter 18-24℃±1℃
Humidity-control range
50-70%±5%
Cooling-capacity adjustment range
0,25,50,75,100 %
Humidification capacity
20 kg/h
Humidification power
15 kW
Compressor type
Hermetic Scroll
Indoor-unit power supply
380V/3N~/50Hz
Fan power
5.5 kW
Cooling input power
23.7 kW
Maximum input power
73.7 kW
Water flow
17.7 m3/h
Water pressure drop
30 kPa
Inlet/outlet pipe diameter
65 DN
Condensing-water pipe diameter
25 DN
Indoor-unit weight
810 kg
Catalog drawing dimension A
1100 mm
Catalog drawing dimension B
2100 mm
Catalog drawing dimension C
1750 mm
Catalog drawing dimension E
2016 mm
Catalog drawing dimension F
1056 mm
Catalog drawing dimension G
360 mm
Catalog drawing dimension H
280 mm
Catalog drawing dimension J
360 mm
Return-air flange
2016*1056 mm
Supply-air flange
360*360*2 mm
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry