Model
OBAIR FLHS-55 — Constant Temperature and Humidity Air-cooled Unitary Air Conditioner (Vertical) R410A
OBAIR FLHS-55 is listed with nominal airflow 10,500 m³/h. No complete L × W × H envelope is claimed for this row.
When to consider this equipment
Use this category for ventilation or air-handling duties. The section sequence, filtration, heating, cooling, recovery and control functions must follow the project air states.
What to include in an enquiry
Provide supply and extract airflow, outdoor and indoor design conditions, external static pressure, filtration class, heating and cooling duties, dimensions and service constraints. The printed designation is not a complete factory order code and must not be used for ordering without confirmation.
Verified technical data
FLHS-55
- Model
- FLHS-55
- Cooling capacity
- 56 kW
- Heat-pump heating capacity
- 57 kW
- Auxiliary electric heating capacity
- 30 kW
- Nominal airflow
- 10500 m3/h
- External static pressure
- 300 Pa
- Temperature-control range
- Summer 22~28℃±1℃, Winter 18~24℃±1℃
- Humidity-control range
- 50~70%±5%
- Humidification capacity
- 15 kg/h
- Humidification power
- 11.7 kW
- Compressor type
- Hermetic Scroll
- Indoor-unit power supply
- 380V/3N~/50Hz
- Fan power
- 4 kW
- Maximum input power
- 62.8 kW
- Condensing-water pipe diameter
- 25 DN
- Outdoor unit model
- SW200
- Outdoor-unit input power
- 17.1 kW
- Liquid-pipe size
- φ15.88*2 mm
- Air-duct size
- φ28.6*2 mm
- Catalog drawing dimension A
- 1050 mm
- Catalog drawing dimension B
- 1950 mm
- Catalog drawing dimension C
- 2030 mm
- Catalog drawing dimension E
- 1866 mm
- Catalog drawing dimension F
- 806 mm
- Catalog drawing dimension G
- 455 mm
- Catalog drawing dimension H
- -- mm
- Catalog drawing dimension J
- 455 mm
- Return-air flange
- 1866*806 mm
- Supply-air flange
- 455*455 mm
On request
3D model not yet available
Selection from project conditions is available on enquiry