Model

OBAIR R410A Heat Pump Type - FLM-WX-***H-E-S1 [65]

OBAIR R410A Heat Pump Type - FLM-WX-***H-E-S1 [65] is listed in the OBAIR catalogue. Length: 2200 mm; Width: 900 mm. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

FLM-WX-***H-E-S1 [65]

Published model pattern
FLM-WX-***H-E-S1
Literal model column token
65
Nominal cooling capacity
66 kW
Nominal heating capacity
72 kW
Cooling input power
20 kW
Heating input power
20.5 kW
Compressor count
2 count
Water volume flow rate
11 m3/h
Water resistance
45 kPa
Inlet/outlet water pipe connection
50 DN
Fan quantity
2 count
Length
2200 mm
Width
900 mm
Height
2020 mm
Unit weight
700 kg
Operating weight
770 kg
Power supply
380V/3N~/50Hz
Compressor type
Flexible Scroll Compressor
Refrigerant type
R410A
Water-side heat exchanger type
Shell and Tube Heat Exchanger
Air-side heat exchanger
Copper tubes with internal threads strung on hydrophilic aluminum foil
Fan type
Axial Flow Fan
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry