Model
OBAIR Four-pipe Modular Air-cooled Heat Pump - FLM-WX-***F-E-D [260]
OBAIR Four-pipe Modular Air-cooled Heat Pump - FLM-WX-***F-E-D [260] is listed in the OBAIR catalogue. Length: 2550 mm; Width: 2200 mm. Confirm the project operating conditions before selection.
When to consider this equipment
Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.
What to include in an enquiry
Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.
Verified technical data
FLM-WX-***F-E-D [260]
- Published model pattern
- FLM-WX-***F-E-D
- Literal model column token
- 260
- Single-cooling capacity
- 260 kW
- Single-cooling input power
- 78.1 kW
- Single-heating capacity
- 280 kW
- Single-heating input power
- 81.2 kW
- Simultaneous-mode cooling capacity
- 265 kW
- Simultaneous-mode heating capacity
- 331 kW
- Simultaneous-mode input power
- 75.0 kW
- Compressor count
- 4 count
- Fan quantity
- 4 count
- Chilled-water flow rate
- 45 m3/h
- Chilled-water resistance
- 48 kPa
- Chilled-water pipe
- 100 DN
- Hot-water heat exchanger type
- Horizontal shell-and-tube heat exchanger/1.0MPa
- Hot-water flow rate
- 57 m3/h
- Hot-water resistance
- 50 kPa
- Hot-water pipe
- 100 DN
- Length
- 2550 mm
- Width
- 2200 mm
- Height
- 2700 mm
- Shipping weight
- 2100 kg
- Operating weight
- 2250 kg
- Power supply
- 380V/3N~/50Hz
- Compressor type
- Compliant Scroll
- Refrigerant type
- R410a
- Fan type
- Low-noise high-efficiency axial fan
- Chilled-water heat exchanger type
- Horizontal shell-and-tube heat exchanger/1.0MPa
On request
3D model not yet available
Selection from project conditions is available on enquiry