Model

OBAIR FLLG***GBH1N | 10630 — R22 heat-pump variant

OBAIR FLLG***GBH1N | 10630 — R22 heat-pump variant is listed in the OBAIR catalogue. Cooling capacity: 625 kW; Heating capacity: 682 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

FLLG***GBH1N | 10630

Cooling capacity
625 kW
Total cooling input power
187.2 kW
Heating capacity
682 kW
Total heating input power
185.4 kW
Power supply
Three-phase, five-wire system AC380V/3N~/ 50Hz
Compressor type
Semi-hermetic screw
Compressor start-up method
Y-△
Compressor count
1 count
Axial-fan type
Water-proof, weather-resistant, low-noise, high-efficiency axial fans
Number of axial fans
10 count
Water-side heat-exchanger type / pressure
Horizontal Shell-and-Tube Heat Exchanger / 1.0MPa
Water-side heat-exchanger flow rate
108 m3/h
Water-side heat-exchanger pressure drop
65 kPa
Inlet/outlet water-pipe connections
125 DN
Outline length
5140 mm
Outline width
2200 mm
Outline height
2820 mm
Throttling mode
Electric Expansion Valve
Refrigerant type
R22
Unit weight
5230 kg
Operating weight
5470 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry