Model

OBAIR FLLG***GAFSN | 20460 — R134a four-pipe variant

OBAIR FLLG***GAFSN | 20460 — R134a four-pipe variant is listed in the OBAIR catalogue. Single-cooling capacity: 458 kW; Single-cooling input power: 140.9 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

FLLG***GAFSN | 20460

Single-cooling capacity
458 kW
Single-cooling input power
140.9 kW
Single-heating capacity
509 kW
Single-heating input power
140.9 kW
Cooling capacity during simultaneous cooling and heating
480 kW
Heating capacity during simultaneous cooling and heating
595 kW
Input power during simultaneous cooling and heating
136.6 kW
Power supply
Three-phase Five-wire System 380V/3N~/ 50Hz
Compressor type
Semi-hermetic Twin-screw Type
Compressor start-up method
Y-Δ
Compressor count
2 count
Axial-flow fan type
Low-noise, high-efficiency, waterproof and weather-resistant AxiFlow Fan
Number of axial-flow fans
8 count
Chilled-water heat-exchanger type / pressure rating
Horizontal Shell-and-tube Heat Exchanger/1.0MPa
Chilled-water flow rate
83 m3/h
Chilled-water pressure drop
55 kPa
Chilled-water inlet/outlet ports
125 DN
Hot-water heat-exchanger type / pressure rating
Horizontal Shell-and-Tube Heat Exchanger/1.0MPa
Hot-water flow rate
102 m3/h
Hot-water pressure drop
60 kPa
Hot-water inlet/outlet ports
125 DN
Outline length
4800 mm
Outline width
2250 mm
Outline height
2790 mm
Unit weight
4980 kg
Operating weight
5160 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry