Model

OBAIR FLLG***GAFSN | 20600 — R134a four-pipe variant

OBAIR FLLG***GAFSN | 20600 — R134a four-pipe variant is listed in the OBAIR catalogue. Single-cooling capacity: 598 kW; Single-cooling input power: 184.2 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

FLLG***GAFSN | 20600

Single-cooling capacity
598 kW
Single-cooling input power
184.2 kW
Single-heating capacity
658 kW
Single-heating input power
182.2 kW
Cooling capacity during simultaneous cooling and heating
627 kW
Heating capacity during simultaneous cooling and heating
769 kW
Input power during simultaneous cooling and heating
177.4 kW
Power supply
Three-phase Five-wire System 380V/3N~/ 50Hz
Compressor type
Semi-hermetic Twin-screw Type
Compressor start-up method
Y-Δ
Compressor count
2 count
Axial-flow fan type
Low-noise, high-efficiency, waterproof and weather-resistant AxiFlow Fan
Number of axial-flow fans
10 count
Chilled-water heat-exchanger type / pressure rating
Horizontal Shell-and-tube Heat Exchanger/1.0MPa
Chilled-water flow rate
108 m3/h
Chilled-water pressure drop
60 kPa
Chilled-water inlet/outlet ports
150 DN
Hot-water heat-exchanger type / pressure rating
Horizontal Shell-and-Tube Heat Exchanger/1.0MPa
Hot-water flow rate
132 m3/h
Hot-water pressure drop
65 kPa
Hot-water inlet/outlet ports
125 DN
Outline length
5970 mm
Outline width
2250 mm
Outline height
2790 mm
Unit weight
6870 kg
Operating weight
7110 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry