Model

OBAIR FLLG***GAFSN | 20670 — R134a four-pipe variant

OBAIR FLLG***GAFSN | 20670 — R134a four-pipe variant is listed in the OBAIR catalogue. Single-cooling capacity: 666 kW; Single-cooling input power: 204.8 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

FLLG***GAFSN | 20670

Single-cooling capacity
666 kW
Single-cooling input power
204.8 kW
Single-heating capacity
731 kW
Single-heating input power
202.3 kW
Cooling capacity during simultaneous cooling and heating
698 kW
Heating capacity during simultaneous cooling and heating
854 kW
Input power during simultaneous cooling and heating
197.2 kW
Power supply
Three-phase Five-wire System 380V/3N~/ 50Hz
Compressor type
Semi-hermetic Twin-screw Type
Compressor start-up method
Y-Δ
Compressor count
2 count
Axial-flow fan type
Low-noise, high-efficiency, waterproof and weather-resistant AxiFlow Fan
Number of axial-flow fans
10 count
Chilled-water heat-exchanger type / pressure rating
Horizontal Shell-and-tube Heat Exchanger/1.0MPa
Chilled-water flow rate
120 m3/h
Chilled-water pressure drop
60 kPa
Chilled-water inlet/outlet ports
150 DN
Hot-water heat-exchanger type / pressure rating
Horizontal Shell-and-Tube Heat Exchanger/1.0MPa
Hot-water flow rate
147 m3/h
Hot-water pressure drop
65 kPa
Hot-water inlet/outlet ports
125 DN
Outline length
5970 mm
Outline width
2250 mm
Outline height
2790 mm
Unit weight
7900 kg
Operating weight
8280 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry