Model

OBAIR R134a Heat Pump Dual Compressor — ZFLS2***GAH1YLG [460]

OBAIR R134a Heat Pump Dual Compressor — ZFLS2***GAH1YLG [460] is listed in the OBAIR catalogue. Cooling capacity: 1620 kW; Heating capacity: 1230 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

ZFLS2***GAH1YLG [460]

Published model pattern
ZFLS2***GAH1YLG
Literal model column token
460
Cooling capacity
1620 kW
Total cooling input power
355.95 kW
Cooling-system COPc
4.55 kW/kW
Heating capacity
1230 kW
Total input power including chilled-water pump — heating
417.75 kW
Heating-system COPh
2.94 kW/kW
Maximum operating current
1003.0 A
Power supply
380V/50Hz/3pH
Compressor type
Semi-hermetic screw type
Compressor count
2 count
Compressor cooling input power
296.8 kW
Compressor cooling EER
5.46 W/W
Compressor heating input power
335 kW
Compressor heating COP
3.67 W/W
Evaporative-condenser type
High-efficiency evaporative condenser (frame and collection basin: aluminum-zinc coated steel sheet; coil heat exchange tubes: carbon steel tube)
Evaporative-condenser quantity
2 count
Cooling-fan quantity
4 count
Total cooling-fan power
16 kW
Total spray-pump power
4.4 kW
Cooling-water makeup rate
2.75 m3/h
Spray-water makeup pipe diameter
25×2 sets DN
Spray-water tank drain pipe diameter
50×2 sets DN
Air-side heat-exchanger type
High-efficiency inner grooved tube + hydrophilic aluminum fins
Air-side fan quantity
20 count
Power per air-side fan
2.2 kW
Total air-side fan power
44 kW
Water-side heat exchanger type
Dry-type shell-and-tube heat exchanger
Water-side heat-exchanger connection diameter
150×2 DN
Chilled-water pump quantity
2 count
Chilled-water pump input power
38.75 kW
External pump head
24 m
Expansion-tank volume
250×2 L
Makeup-water pipe diameter
25×2 DN
Chilled-water flow rate
278.6 m3/h
Hydraulic-module connection diameter
150×2 DN
Length
24120 mm
Width
2500 mm
Height
2830 mm
Shipping weight
24220 kg
Operating weight
31540 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry