Model

OBAIR GWP Series Dual Compressor — GWP****MARSN [2310]

OBAIR GWP Series Dual Compressor — GWP****MARSN [2310] is listed in the OBAIR catalogue. Cooling capacity: 1050 kW; Heating capacity: 1071 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

GWP****MARSN [2310]

Published model pattern
GWP****MARSN
Literal model column token
2310
Cooling capacity
1050 kW
Cooling input power
165.5 kW
Cooling input current
295.4 A
Cooling EER
6.34 W/W
Cooling evaporator water flow rate
181 m3/h
Cooling evaporator water pressure drop
78 kPa
Cooling evaporator pipe size
DN200 mm
Cooling condenser water flow rate
226 m3/h
Cooling condenser water pressure drop
57 kPa
Cooling condenser pipe size
DN200 mm
Heating capacity
1071 kW
Heating input power
214.5 kW
Heating input current
382.9 A
Heating COP
4.99 W/W
Heating evaporator water flow rate
226 m3/h
Heating evaporator water pressure drop
85 kPa
Heating evaporator pipe size
DN200 mm
Heating condenser water flow rate
181 m3/h
Heating condenser water pressure drop
57 kPa
Heating condenser pipe size
DN200 mm
Annual comprehensive performance coefficient
5.75 kW/kW
Energy-efficiency rating
Level 1
Compressor count
2 count
Compressor type
Semi-closed Twin-screw Compressor
Compressor start-up method
Star-Delta
Partial-load energy regulation range
Infinite Capacity Control
Maximum operating current
586 A
Unit start-up current
665 A
Refrigerant type
R134a
Refrigerant charge
328 kg
Length
4800 mm
Width
1400 mm
Height
2130 mm
Unit weight
6950 kg
Operating weight
7330 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry