Model

OBAIR GWP Series Dual Compressor — GWP****MARSN [2570]

OBAIR GWP Series Dual Compressor — GWP****MARSN [2570] is listed in the OBAIR catalogue. Cooling capacity: 2008 kW; Heating capacity: 2048 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

GWP****MARSN [2570]

Published model pattern
GWP****MARSN
Literal model column token
2570
Cooling capacity
2008 kW
Cooling input power
317.6 kW
Cooling input current
568.5 A
Cooling EER
6.32 W/W
Cooling evaporator water flow rate
345 m3/h
Cooling evaporator water pressure drop
81 kPa
Cooling evaporator pipe size
DN250 mm
Cooling condenser water flow rate
432 m3/h
Cooling condenser water pressure drop
71 kPa
Cooling condenser pipe size
DN250 mm
Heating capacity
2048 kW
Heating input power
401.0 kW
Heating input current
715.8 A
Heating COP
5.11 W/W
Heating evaporator water flow rate
432 m3/h
Heating evaporator water pressure drop
94 kPa
Heating evaporator pipe size
DN250 mm
Heating condenser water flow rate
345 m3/h
Heating condenser water pressure drop
67 kPa
Heating condenser pipe size
DN250 mm
Annual comprehensive performance coefficient
5.79 kW/kW
Energy-efficiency rating
Level 1
Compressor count
2 count
Compressor type
Semi-closed Twin-screw Compressor
Compressor start-up method
Star-Delta
Partial-load energy regulation range
Infinite Capacity Control
Maximum operating current
1095 A
Unit start-up current
1279 A
Refrigerant type
R134a
Refrigerant charge
627 kg
Length
5050 mm
Width
1800 mm
Height
2240 mm
Unit weight
10130 kg
Operating weight
10890 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry