Model

OBAIR GWP Series Dual Compressor — GWP****MARSN [2660]

OBAIR GWP Series Dual Compressor — GWP****MARSN [2660] is listed in the OBAIR catalogue. Cooling capacity: 2404 kW; Heating capacity: 2452 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

GWP****MARSN [2660]

Published model pattern
GWP****MARSN
Literal model column token
2660
Cooling capacity
2404 kW
Cooling input power
379.7 kW
Cooling input current
679.7 A
Cooling EER
6.33 W/W
Cooling evaporator water flow rate
413 m3/h
Cooling evaporator water pressure drop
89 kPa
Cooling evaporator pipe size
DN250 mm
Cooling condenser water flow rate
517 m3/h
Cooling condenser water pressure drop
71 kPa
Cooling condenser pipe size
DN250 mm
Heating capacity
2452 kW
Heating input power
472.7 kW
Heating input current
843.8 A
Heating COP
5.19 W/W
Heating evaporator water flow rate
517 m3/h
Heating evaporator water pressure drop
99 kPa
Heating evaporator pipe size
DN250 mm
Heating condenser water flow rate
413 m3/h
Heating condenser water pressure drop
76 kPa
Heating condenser pipe size
DN250 mm
Annual comprehensive performance coefficient
5.83 kW/kW
Energy-efficiency rating
Level 1
Compressor count
2 count
Compressor type
Semi-closed Twin-screw Compressor
Compressor start-up method
Star-Delta
Partial-load energy regulation range
Infinite Capacity Control
Maximum operating current
1291 A
Unit start-up current
1529 A
Refrigerant type
R134a
Refrigerant charge
751 kg
Length
5750 mm
Width
1900 mm
Height
2240 mm
Unit weight
11030 kg
Operating weight
11860 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry