Model

OBAIR GWP Series Single Compressor P163 — GWP****MARSN [1120]

OBAIR GWP Series Single Compressor P163 — GWP****MARSN [1120] is listed in the OBAIR catalogue. Cooling capacity: 418 kW; Heating capacity: 431 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

GWP****MARSN [1120]

Published model pattern
GWP****MARSN
Literal model column token
1120
Cooling capacity
418 kW
Cooling input power
65.5 kW
Cooling input current
115.3 A
Cooling EER
6.38 W/W
Cooling evaporator water flow rate
72 m3/h
Cooling evaporator water pressure drop
50 kPa
Cooling evaporator pipe size
DN125 mm
Cooling condenser water flow rate
90 m3/h
Cooling condenser water pressure drop
45 kPa
Cooling condenser pipe size
DN125 mm
Heating capacity
431 kW
Heating input power
87.1 kW
Heating input current
153.3 A
Heating COP
4.95 W/W
Heating evaporator water flow rate
90 m3/h
Heating evaporator water pressure drop
69 kPa
Heating evaporator pipe size
DN125 mm
Heating condenser water flow rate
72 m3/h
Heating condenser water pressure drop
47 kPa
Heating condenser pipe size
DN125 mm
Annual comprehensive performance coefficient
5.75 kW/kW
Energy-efficiency rating
Level 1
Compressor count
1 count
Compressor type
Semi-closed Twin-screw Compressor
Compressor start-up method
Star-Delta
Partial-load energy regulation range
Infinite Capacity Control
Maximum operating current
233 A
Unit start-up current
352 A
Refrigerant type
R134a
Refrigerant charge
131 kg
Length
3000 mm
Width
1600 mm
Height
1750 mm
Unit weight
2630 kg
Operating weight
2770 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry