Model

OBAIR GWP Series Single Compressor P163 — GWP****MARSN [1170]

OBAIR GWP Series Single Compressor P163 — GWP****MARSN [1170] is listed in the OBAIR catalogue. Cooling capacity: 594 kW; Heating capacity: 606 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

GWP****MARSN [1170]

Published model pattern
GWP****MARSN
Literal model column token
1170
Cooling capacity
594 kW
Cooling input power
94.5 kW
Cooling input current
167.3 A
Cooling EER
6.29 W/W
Cooling evaporator water flow rate
102 m3/h
Cooling evaporator water pressure drop
57 kPa
Cooling evaporator pipe size
DN125 mm
Cooling condenser water flow rate
128 m3/h
Cooling condenser water pressure drop
64 kPa
Cooling condenser pipe size
DN125 mm
Heating capacity
606 kW
Heating input power
118.8 kW
Heating input current
210.3 A
Heating COP
5.1 W/W
Heating evaporator water flow rate
128 m3/h
Heating evaporator water pressure drop
75 kPa
Heating evaporator pipe size
DN125 mm
Heating condenser water flow rate
102 m3/h
Heating condenser water pressure drop
50 kPa
Heating condenser pipe size
DN125 mm
Annual comprehensive performance coefficient
5.76 kW/kW
Energy-efficiency rating
Level 1
Compressor count
1 count
Compressor type
Semi-closed Twin-screw Compressor
Compressor start-up method
Star-Delta
Partial-load energy regulation range
Infinite Capacity Control
Maximum operating current
320 A
Unit start-up current
510 A
Refrigerant type
R134a
Refrigerant charge
185 kg
Length
3000 mm
Width
1600 mm
Height
1750 mm
Unit weight
3400 kg
Operating weight
3610 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry