Model

OBAIR WHP Series Dual Compressor — WHP****MARSN [2410]

OBAIR WHP Series Dual Compressor — WHP****MARSN [2410] is listed in the OBAIR catalogue. Cooling capacity: 1488 kW; Heating capacity: 1531 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

WHP****MARSN [2410]

Published model pattern
WHP****MARSN
Literal model column token
2410
Cooling capacity
1488 kW
Cooling input power
230.3 kW
Cooling input current
411.1 A
Cooling EER
6.46 W/W
Cooling evaporator water flow rate
256 m3/h
Cooling evaporator water pressure drop
76 kPa
Cooling evaporator pipe size
DN200 mm
Cooling condenser water flow rate
320 m3/h
Cooling condenser water pressure drop
26 kPa
Cooling condenser pipe size
DN200 mm
Heating capacity
1531 kW
Heating input power
291.6 kW
Heating input current
520.5 A
Heating COP
5.25 W/W
Heating evaporator water flow rate
319.9 m3/h
Heating evaporator water pressure drop
28 kPa
Heating evaporator pipe size
DN200 mm
Heating condenser water flow rate
255.9 m3/h
Heating condenser water pressure drop
55 kPa
Heating condenser pipe size
DN200 mm
Annual comprehensive performance coefficient
5.93 kW/kW
Energy-efficiency rating
Level 2
Compressor count
2 count
Compressor type
Semi-closed Twin-screw Compressor
Compressor start-up method
Star-Delta
Partial-load energy regulation range
Infinite Capacity Control
Maximum operating current
796 A
Unit start-up current
925 A
Refrigerant type
R134a
Refrigerant charge
460 kg
Length
4950 mm
Width
1600 mm
Height
2130 mm
Unit weight
7550 kg
Operating weight
8090 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry