Model

OBAIR WHP Series Single Compressor P160 — WHP****MARSN [1110]

OBAIR WHP Series Single Compressor P160 — WHP****MARSN [1110] is listed in the OBAIR catalogue. Cooling capacity: 387 kW; Heating capacity: 398 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

WHP****MARSN [1110]

Published model pattern
WHP****MARSN
Literal model column token
1110
Cooling capacity
387 kW
Cooling input power
60.0 kW
Cooling input current
105.6 A
Cooling EER
6.45 W/W
Cooling evaporator water flow rate
67 m3/h
Cooling evaporator water pressure drop
47 kPa
Cooling evaporator pipe size
DN125 mm
Cooling condenser water flow rate
40 m3/h
Cooling condenser water pressure drop
24 kPa
Cooling condenser pipe size
DN125 mm
Heating capacity
398 kW
Heating input power
76 kW
Heating input current
133.8 A
Heating COP
5.24 W/W
Heating evaporator water flow rate
39.9 m3/h
Heating evaporator water pressure drop
21 kPa
Heating evaporator pipe size
DN125 mm
Heating condenser water flow rate
66.6 m3/h
Heating condenser water pressure drop
49 kPa
Heating condenser pipe size
DN125 mm
Annual comprehensive performance coefficient
5.92 kW/kW
Energy-efficiency rating
Level 2
Compressor count
1 count
Compressor type
Semi-closed Twin-screw Compressor
Compressor start-up method
Star-Delta
Partial-load energy regulation range
Infinite Capacity Control
Maximum operating current
203 A
Unit start-up current
322 A
Refrigerant type
R134a
Refrigerant charge
120 kg
Length
3000 mm
Width
1600 mm
Height
1750 mm
Unit weight
2550 kg
Operating weight
2960 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry