Model

OBAIR WHP Series Single Compressor P160 — WHP****MARSN [1150]

OBAIR WHP Series Single Compressor P160 — WHP****MARSN [1150] is listed in the OBAIR catalogue. Cooling capacity: 531 kW; Heating capacity: 546 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

WHP****MARSN [1150]

Published model pattern
WHP****MARSN
Literal model column token
1150
Cooling capacity
531 kW
Cooling input power
81.9 kW
Cooling input current
144.1 A
Cooling EER
6.48 W/W
Cooling evaporator water flow rate
91 m3/h
Cooling evaporator water pressure drop
48 kPa
Cooling evaporator pipe size
DN125 mm
Cooling condenser water flow rate
55 m3/h
Cooling condenser water pressure drop
21 kPa
Cooling condenser pipe size
DN125 mm
Heating capacity
546 kW
Heating input power
104.7 kW
Heating input current
184.3 A
Heating COP
5.21 W/W
Heating evaporator water flow rate
54.7 m3/h
Heating evaporator water pressure drop
23 kPa
Heating evaporator pipe size
DN125 mm
Heating condenser water flow rate
91.3 m3/h
Heating condenser water pressure drop
49 kPa
Heating condenser pipe size
DN125 mm
Annual comprehensive performance coefficient
5.93 kW/kW
Energy-efficiency rating
Level 2
Compressor count
1 count
Compressor type
Semi-closed Twin-screw Compressor
Compressor start-up method
Star-Delta
Partial-load energy regulation range
Infinite Capacity Control
Maximum operating current
280 A
Unit start-up current
440 A
Refrigerant type
R134a
Refrigerant charge
164 kg
Length
3000 mm
Width
1600 mm
Height
1750 mm
Unit weight
3300 kg
Operating weight
3490 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry