Model

OBAIR WHP Series Single Compressor P161 — WHP****MARSN [1340]

OBAIR WHP Series Single Compressor P161 — WHP****MARSN [1340] is listed in the OBAIR catalogue. Cooling capacity: 1215 kW; Heating capacity: 1250 kW. Confirm the project operating conditions before selection.

When to consider this equipment

Use this category for chilled-water or heat-pump duties after the design temperatures, capacity, ambient or source conditions and hydraulic arrangement are known.

What to include in an enquiry

Provide cooling and heating duty, water temperatures and flow, ambient or source range, refrigerant restrictions, electrical supply, sound limits and redundancy requirements.

Verified technical data

WHP****MARSN [1340]

Published model pattern
WHP****MARSN
Literal model column token
1340
Cooling capacity
1215 kW
Cooling input power
186.5 kW
Cooling input current
332.0 A
Cooling EER
6.51 W/W
Cooling evaporator water flow rate
209 m3/h
Cooling evaporator water pressure drop
77 kPa
Cooling evaporator pipe size
DN200 mm
Cooling condenser water flow rate
125 m3/h
Cooling condenser water pressure drop
31 kPa
Cooling condenser pipe size
DN200 mm
Heating capacity
1250 kW
Heating input power
234.4 kW
Heating input current
417.2 A
Heating COP
5.33 W/W
Heating evaporator water flow rate
125.1 m3/h
Heating evaporator water pressure drop
33 kPa
Heating evaporator pipe size
DN200 mm
Heating condenser water flow rate
209.0 m3/h
Heating condenser water pressure drop
59 kPa
Heating condenser pipe size
DN200 mm
Annual comprehensive performance coefficient
5.99 kW/kW
Energy-efficiency rating
Level 2
Compressor count
1 count
Compressor type
Semi-closed Twin-screw Compressor
Compressor start-up method
Star-Delta
Partial-load energy regulation range
Infinite Capacity Control
Maximum operating current
638 A
Unit start-up current
1013 A
Refrigerant type
R134a
Refrigerant charge
375 kg
Length
3550 mm
Width
1600 mm
Height
2100 mm
Unit weight
4800 kg
Operating weight
5210 kg
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry