Verified technical data
ZYJ-06V
- Configuration variant
- Performance Parameters — compact medical direct expansion air handling unit
- Airflow rate
- 6000 m3/h
- Fresh air volume
- 1600 m3/h
- External static pressure
- 550 Pa
- Chilled-water cooling capacity
- 42 kW
- Water supply
- 7.2 t/h
- Chilled-water pipe diameter
- DN40
- Direct-evaporation cooling capacity
- 42.5 kW
- Outdoor-unit model
- SW150*1
- Direct-evaporation total power
- 9.85*2 kW
- Outdoor-unit length
- 1870 mm
- Outdoor-unit width
- 900 mm
- Outdoor-unit height
- 1760 mm
- Liquid supply pipe × quantity
- Φ12.7*2 mm × count
- Return pipe × quantity
- Φ12.7*2 mm × count
- Condensing-water pipe
- DN32
- Heating capacity
- 45 kW
- Humidification type
- Electrode
- Humidifier capacity
- 18 kg/h
- Humidifier power
- 13.5 kW
- Electric reheating type
- PTC
- Electric reheating power
- 25 kW
- Power supply
- 380V/3N~/50Hz
- Motor power
- 3 kW
- Overall size L×H×T
- 2300*2160*900 mm
- Operating weight
- 620 kg
- Return-air inlet dimensions
- Flange 560*450 mm
- Fresh-air inlet dimensions
- Flange 300*150 mm
- Supply-air outlet dimensions
- Flange 700*450 mm
- Filter configuration
- G4+F8
On request
3D model not yet available