Model

OBAIR ZYJ-25 — JX fresh-air unit

OBAIR ZYJ-25 is a catalogue-listed medical and clean-room air handling unit with a published L × W × H envelope of 4,600 × 2,050 × 1,830 mm.

When to consider this equipment

Use this category for ventilation or air-handling duties. The section sequence, filtration, heating, cooling, recovery and control functions must follow the project air states.

What to include in an enquiry

Provide supply and extract airflow, outdoor and indoor design conditions, external static pressure, filtration class, heating and cooling duties, dimensions and service constraints. Source coverage for this row is partial; missing values remain unfilled.

Verified technical data

ZYJ-25

Configuration variant
JX Technical Parameters (Fresh Air Unit)
Rated airflow rate
25000 m3/h
Airflow rate range
22500.0–27000.0 m3/h
External static pressure
550 Pa
Motor power
15 kW
Two-pipe cooling capacity, return-air condition, 2R
325 kW
Two-pipe cooling capacity, return-air condition, 4R
406.3 kW
Two-pipe cooling capacity, return-air condition, 6R
438.8 kW
42°C hot-water coil heating capacity, 1R
100.2 kW
42°C hot-water coil heating capacity, 2R
152.4 kW
42°C hot-water coil heating capacity, 4R
231.6 kW
60°C hot-water coil heating capacity, 1R
179 kW
60°C hot-water coil heating capacity, 2R
270.3 kW
60°C hot-water coil heating capacity, 4R
410.8 kW
Steam-coil heating capacity, 1R
194.0 kW
Steam-coil heating capacity, 2R
314.3 kW
Return-air inlet dimensions
1960*1510 mm
Supply-air outlet dimensions
1500*810 mm
Condensing-water pipe
DN32
Dehumidification and reheating
2*6HP
JX1 unit length
4600 mm
JX1 unit width
2050 mm
JX1 unit height
1830 mm
JX2 unit length
4800 mm
JX2 unit width
2050 mm
JX2 unit height
1830 mm
Manufacturer source

On request

3D model not yet available

Selection from project conditions is available on enquiry