Skip to content

By function

Water and glycol air cooling coils

Air cooling with water or glycol. Check the operating duty, air humidity and condensate requirements together.

UPGR archive 3D view of the КВО 100-50 water cooling coil: casing, fins and connections
Owned UPGR archive 3D visualization of КВО 100-50. The view shows the exterior of a water cooling coil; internal circuits, operating conditions and the ordered configuration are defined during selection.

Inside the heat exchanger

A liquid cooling coil takes heat from the air. Condensation occurs when the surface is below the air dew point, requiring collection and drainage; a droplet eliminator depends on the design.

Read the following parts as a typical CuAl coil anatomy. Actual circuiting and accessories vary with the equipment and duty.

Open a larger image: Exploded view of a finned-tube section. Individual parts below illustrate their function; their dimensions and arrangement vary between coil designs.
Exploded view of a finned-tube section. Individual parts below illustrate their function; their dimensions and arrangement vary between coil designs.
Open a larger image: Copper tubes

Heat-transfer core

Copper tubes

Channels carrying the working fluid through the finned core.

Separate the fluid from air and conduct heat to or from the fins.

Core element of a CuAl finned-tube coil.

What to inspect

Leak traces, corrosion or visible damage.

Open a larger image: Aluminium fins

Heat-transfer core

Aluminium fins

Thin metal sheets in thermal contact with the tubes.

Enlarge the surface exchanging heat with air.

Core element; spacing and profile vary.

What to inspect

Dirt deposits, damaged passages or corrosion.

Open a larger image: Return bends and hairpins

Depends on circuit and construction

Return bends and hairpins

Curved tube sections connecting successive passes.

Turn the flow and form the coil circuit.

Layout-dependent; an integral hairpin and a separate return bend are different constructions.

What to inspect

Damaged bends or leakage at joints.

Open a larger image: Headers and connections

Depends on circuit and construction

Headers and connections

Manifolds linking multiple tube circuits to external connections.

Distribute or collect the working fluid.

Arrangement depends on circuiting; headers are not identical to a DX distributor.

What to inspect

Corrosion, joint damage or leak traces.

Open a larger image: Frame, casing and tube supports

Depends on circuit and construction

Frame, casing and tube supports

End plates and supporting casing around the core.

Support the core and provide mounting interfaces.

Common; casing styles include end-plates-only constructions.

What to inspect

Deformation, corrosion or damaged mountings.

Open a larger image: Condensate tray and drain

Where required by the duty

Condensate tray and drain

A collection surface beneath a coil that produces condensate.

Collect and remove condensed water.

Needed for wet cooling; often part of the equipment section.

What to inspect

Standing water, deposits, corrosion or leakage.

Open a larger image: Droplet eliminator

Where required by the duty

Droplet eliminator

A downstream separator for droplets carried by the airflow.

Intercepts droplets and lets collected water drain.

Conditional on carryover risk and equipment design; not every cooling coil has one.

What to inspect

Contamination, damage or water carryover.

Open a larger image: UPGR 3D model of a coil with piping, a pump and control equipment

External piping

External hydronic assembly

A separate piping package with valves and, where specified, a pump.

Controls fluid delivery and connects the coil to the system.

External to the finned core; component list follows the circuit design.

What to inspect

Leaks or control faults are system issues, not proof of coil damage.

Condition signs help identify what needs inspection; they do not identify the fault by themselves. Service methods and intervals follow the equipment manual.

Dry and wet cooling

A dry operating condition has no condensation on the coil surface. When moist air is cooled sufficiently, some of its moisture may condense. Entering air temperature alone therefore does not fully describe the duty: humidity is needed to assess cooling and dehumidification. Establish the condition from the specified duty, not from the product name.

IN PRACTICE

Cooling and condensate: two different checks

Moisture removal depends on air humidity and surface temperature. Not every cooling duty produces condensate.

  1. Air entering

    Temperature, humidity and flow.

  2. Cooling surface

    Air loses heat; moisture may condense.

  3. Collection + drain

    Check the pan, drainage and carryover conditions.

The image shows an archive KVO water cooling coil. Glycol duty requires a separate selection; pan, drainage and supply scope are agreed for the order.

Water and glycol solutions

The word glycol does not specify the fluid mixture. Provide the solution type, concentration and operating temperatures. Thermal performance and water-side pressure drop are assessed for that declared fluid. Two coils are not automatically interchangeable because both provide liquid cooling or have the same face area.

Condensate and supply scope

Where condensation is possible, review collection and drainage as part of the equipment arrangement. Do not assume that a drain pan or drainage components are included with the coil. Check coil position, airflow direction, available space and connections. For replacement, photographs of the surrounding installation are useful alongside images of the finned surface.

REVIEW THE RESULT

What to check in a cooling coil selection

Entering and leaving air

Provide entering air temperature and humidity, together with the required leaving condition. The result should identify the dry or wet operating condition and the resulting air state, as well as capacity.

Exact fluid specification

For glycol, state the type and concentration; for every duty, provide temperatures and the known liquid flow. Compare alternatives using the same fluid, with its composition and pressure drop recorded on the selection sheet.

Condensate drainage

For wet operation, check the coil position, drain pan and condensate drainage path within the unit. The supply scope should identify which components remain in place and which need to be included in the enquiry.

Standard sizes, drawings and model cards

Compare the recovered series by nominal opening, frame and casing depth. Each model has its own drawing and render; final suitability depends on the operating duty and connections.

The catalogue includes liquid-coil dimensions. Glycol concentration and duty require a separate selection; archived water ratings cannot be used unchanged.

SELECTION INPUTS

Inputs to prepare

  • Entering airflow, air temperature and humidity.
  • Required leaving air condition or cooling duty.
  • Water, or the glycol type and concentration.
  • Liquid temperatures and flow rate if known.
  • Air-side and liquid-side pressure-drop limits.
  • Installation envelope, connections and condensate drainage arrangement.

What do you need to do?

Select a new coil

Define operating conditions first. The input checklist above describes the data needed for this application. The enquiry form adapts to the selected duty; it does not calculate a coil rating.

Replace an existing coil

Add the equipment nameplate, photographs, overall and finned dimensions, airflow direction, connections and access constraints. Matching the envelope alone does not confirm performance or compatibility.

Prepare an OEM specification

Separate fixed interfaces from dimensions open to change. Attach the current drawing revision, duty points, material requirements, quantity and acceptance criteria. Manufacturing feasibility is confirmed for the specific specification.

Final performance, materials and compatibility require a project-specific selection and an approved drawing.

Questions about this application

Why is humidity needed for a cooling coil?

Humidity helps establish whether cooling will involve condensation and dehumidification. The same air temperatures can represent different heat and moisture removal duties.

Can water be replaced with glycol without reviewing the selection?

The change needs to be checked for the specific mixture and duty. Naming glycol in an enquiry does not establish that an existing coil will retain the same capacity and pressure drop.

Is an air cooling coil the same as a chiller?

No. This page describes a heat exchange section through which air and liquid pass. The source of chilled liquid and the other system equipment have their own specifications and supply boundaries.