36 MODELS · 9 NOMINAL OPENINGS
Standard sizes of copper–aluminium heat exchangers Choose a function and nominal opening, then compare the frame, casing and connections in the model card. These are sizes of the illustrated series, not a universal interchangeability standard.
The coils in this catalogue have copper tubes and aluminium fins. “Aluminium” here describes the fins; it does not identify an all-aluminium coil.
Water cooling coils 9 models Refrigerant cooling coils 9 models Liquid heating coils 18 variants
Compare the nine nominal sizes Models and dimensions Selection requirements Questions about standard coil sizes
Compare the nine nominal sizes Each cell links to the exact model card. Read dimensions as frame width × height / casing depth, in mm; connections may project beyond these dimensions.
On a narrow screen, scroll the table horizontally.
“?” marks a dimension with conflicting source values. Open the model card to see both values.
Heater variants 2 and 3. Do not transfer a rating between variants. Matching performance-table rows are available for variant 2; variant 3 has drawings, but lacks its own table. A separate historical product description is identified in the relevant card.
Models and dimensions Coil type All types Water cooling coils Refrigerant cooling coils Liquid heating coils Nominal opening, mm All nine sizes 400 × 200 500 × 250 500 × 300 600 × 300 600 × 350 700 × 400 800 × 500 900 × 500 1000 × 500 Reset filters
Models shown: 36 / 36
Existing 3D renders show the connection side. They are static illustrations; connection handedness and exact geometry must be checked on the agreed drawing.
No models match these filters.
Nominal opening 400 × 200 mm
Frame dimensions 520 × 340 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 400 mm
Nominal height H 200 mm
Frame width B1 520 mm
Frame height H1 340 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 1000 m³/h
Cooling capacity 4.2 kW
Maximum stated mass 16 kg
Water flow 0.81 m³/h
Hydraulic pressure drop 3.48 kPa
Nominal opening 500 × 250 mm
Frame dimensions 620 × 390 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 500 mm
Nominal height H 250 mm
Frame width B1 620 mm
Frame height H1 390 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 1600 m³/h
Cooling capacity 6.8 kW
Maximum stated mass 19 kg
Water flow 1.29 m³/h
Hydraulic pressure drop 5.6 kPa
Nominal opening 500 × 300 mm
Frame dimensions 620 × 440 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 500 mm
Nominal height H 300 mm
Frame width B1 620 mm
Frame height H1 440 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 1900 m³/h
Cooling capacity 8 kW
Maximum stated mass 21 kg
Water flow 1.53 m³/h
Hydraulic pressure drop 5.69 kPa
Nominal opening 600 × 300 mm
Frame dimensions 720 × 440 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 600 mm
Nominal height H 300 mm
Frame width B1 720 mm
Frame height H1 440 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 2300 m³/h
Cooling capacity 9.7 kW
Maximum stated mass 23 kg
Water flow 1.86 m³/h
Hydraulic pressure drop 8.73 kPa
Nominal opening 600 × 350 mm
Frame dimensions 720 × 490 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 600 mm
Nominal height H 350 mm
Frame width B1 720 mm
Frame height H1 490 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 2700 m³/h
Cooling capacity 11.4 kW
Maximum stated mass 25 kg
Water flow 2.19 m³/h
Hydraulic pressure drop 9.58 kPa
Nominal opening 700 × 400 mm
Frame dimensions 820 × 540 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 700 mm
Nominal height H 400 mm
Frame width B1 820 mm
Frame height H1 540 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 3600 m³/h
Cooling capacity 15.2 kW
Maximum stated mass 28 kg
Water flow 2.19 m³/h
Hydraulic pressure drop 13.71 kPa
Nominal opening 800 × 500 mm
Frame dimensions 920 × 640 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 800 mm
Nominal height H 500 mm
Frame width B1 920 mm
Frame height H1 640 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 5100 m³/h
Cooling capacity 21.5 kW
Maximum stated mass 38 kg
Water flow 4.12 m³/h
Hydraulic pressure drop 20.79 kPa
Nominal opening 900 × 500 mm
Frame dimensions 1035 × 655 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 900 mm
Nominal height H 500 mm
Frame width B1 1035 mm
Frame height H1 655 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 5700 m³/h
Cooling capacity 24 kW
Maximum stated mass 42 kg
Water flow 4.6 m³/h
Hydraulic pressure drop 27.56 kPa
Nominal opening 1000 × 500 mm
Frame dimensions 1135 × 655 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 1000 mm
Nominal height H 500 mm
Frame width B1 1135 mm
Frame height H1 655 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 6300 m³/h
Cooling capacity 26.6 kW
Maximum stated mass 45 kg
Water flow 5.08 m³/h
Hydraulic pressure drop 29.09 kPa
Nominal opening 400 × 200 mm
Frame dimensions 564 × 283 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 400 mm
Nominal height H 200 mm
Frame width B1 564 mm
Frame height H1 283 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 1000 m³/h
Cooling capacity 3.5 kW
Maximum stated mass 16 kg
Nominal opening 500 × 250 mm
Frame dimensions 664 × 333 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 500 mm
Nominal height H 250 mm
Frame width B1 664 mm
Frame height H1 333 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 1600 m³/h
Cooling capacity 6.3 kW
Maximum stated mass 18 kg
Nominal opening 500 × 300 mm
Frame dimensions 664 × 383 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 500 mm
Nominal height H 300 mm
Frame width B1 664 mm
Frame height H1 383 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 1900 m³/h
Cooling capacity 7.1 kW
Maximum stated mass 19 kg
Nominal opening 600 × 300 mm
Frame dimensions 764 × 383 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 600 mm
Nominal height H 300 mm
Frame width B1 764 mm
Frame height H1 383 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 2300 m³/h
Cooling capacity 9 kW
Maximum stated mass 21 kg
Nominal opening 600 × 350 mm
Frame dimensions 764 × 433 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 600 mm
Nominal height H 350 mm
Frame width B1 764 mm
Frame height H1 433 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 2700 m³/h
Cooling capacity 10.1 kW
Maximum stated mass 23 kg
Nominal opening 700 × 400 mm
Frame dimensions 864 × 483 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 700 mm
Nominal height H 400 mm
Frame width B1 864 mm
Frame height H1 483 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 3600 m³/h
Cooling capacity 13.8 kW
Maximum stated mass 26 kg
Nominal opening 800 × 500 mm
Frame dimensions 964 × 583 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 800 mm
Nominal height H 500 mm
Frame width B1 964 mm
Frame height H1 583 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 5100 m³/h
Cooling capacity 17.7 kW
Maximum stated mass 32 kg
Nominal opening 900 × 500 mm
Frame dimensions 1074 × 598 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 900 mm
Nominal height H 500 mm
Frame width B1 1074 mm
Frame height H1 598 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 5700 m³/h
Cooling capacity 20.5 kW
Maximum stated mass 36 kg
Nominal opening 1000 × 500 mm
Frame dimensions 1174 × 598 mm
Casing depth 300 mm
All drawing dimensions
Nominal width B 1000 mm
Nominal height H 500 mm
Frame width B1 1174 mm
Frame height H1 598 mm
Casing depth L 300 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Airflow 6300 m³/h
Cooling capacity 23.4 kW
Maximum stated mass 42 kg
Nominal opening 400 × 200 mm
Frame dimensions 440 × 240 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 400 mm
Nominal height B 200 mm
Frame width K 440 mm
Frame height E 240 mm
Casing depth C 150 mm
Connection-to-frame span L 575 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Row count 2
Fin spacing 2.5 mm
Connection designation G1
Circuit count 4
Heat exchange area 2.6 m²
Airflow 850 m³/h
Hydraulic pressure drop 3.3 kPa
Heating capacity 18 kW
Internal volume 0.47 L
Mass 2.83 kg
Nominal opening 400 × 200 mm
Frame dimensions 440 × 240 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 400 mm
Nominal height B 200 mm
Frame width K 440 mm
Frame height E 240 mm
Casing depth C 150 mm
Connection-to-frame span L 575 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics A matching performance table for this variant is not available. Request selection for your duty.
Nominal opening 500 × 250 mm
Frame dimensions 540 × 290 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 500 mm
Nominal height B 250 mm
Frame width K 540 mm
Frame height E 290 mm
Casing depth C 150 mm
Connection-to-frame span L 675 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Row count 2
Fin spacing 2.5 mm
Connection designation G1
Circuit count 5
Heat exchange area 4 m²
Airflow 1350 m³/h
Hydraulic pressure drop 5.8 kPa
Heating capacity 29 kW
Internal volume 0.72 L
Mass 3.99 kg
Nominal opening 500 × 250 mm
Frame dimensions 540 × 290 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 500 mm
Nominal height B 250 mm
Frame width K 540 mm
Frame height E 290 mm
Casing depth C 150 mm
Connection-to-frame span L 675 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics A matching performance table for this variant is not available. Request selection for your duty.
Nominal opening 500 × 300 mm
Frame dimensions 540 × 340 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 500 mm
Nominal height B 300 mm
Frame width K 540 mm
Frame height E 340 mm
Casing depth C 150 mm
Connection-to-frame span L 675 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Row count 2
Fin spacing 2.5 mm
Connection designation G1
Circuit count 6
Heat exchange area 4.8 m²
Airflow 1600 m³/h
Hydraulic pressure drop 5.7 kPa
Heating capacity 34 kW
Internal volume 0.87 L
Mass 4.68 kg
Nominal opening 500 × 300 mm
Frame dimensions 540 × 340 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 500 mm
Nominal height B 300 mm
Frame width K 540 mm
Frame height E 340 mm
Casing depth C 150 mm
Connection-to-frame span L 675 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics A matching performance table for this variant is not available. Request selection for your duty.
Nominal opening 600 × 300 mm
Frame dimensions 660 × 340 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 600 mm
Nominal height B 300 mm
Frame width K 660 mm
Frame height E 340 mm
Casing depth C 150 mm
Connection-to-frame span L 775 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Row count 2
Fin spacing 2.5 mm
Connection designation G1
Circuit count 6
Heat exchange area 5.8 m²
Airflow 1900 m³/h
Hydraulic pressure drop 8.9 kPa
Heating capacity 41 kW
Internal volume 1.03 L
Mass 5.34 kg
Nominal opening 600 × 300 mm
Frame dimensions 660 × 340 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 600 mm
Nominal height B 300 mm
Frame width K 660 mm
Frame height E 340 mm
Casing depth C 150 mm
Connection-to-frame span L 775 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics A matching performance table for this variant is not available. Request selection for your duty.
Dimension needs confirmation: E — Table 340, Drawing 390 mm.
Nominal opening 600 × 350 mm
Frame dimensions 660 × ? mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 600 mm
Nominal height B 350 mm
Frame width K 660 mm
Frame height E Dimension needs confirmation Table: 340; Drawing: 390 mm
Casing depth C 150 mm
Connection-to-frame span L 775 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Row count 2
Fin spacing 2.5 mm
Connection designation G1
Circuit count 7
Heat exchange area 6.7 m²
Airflow 2200 m³/h
Hydraulic pressure drop 8.8 kPa
Heating capacity 48 kW
Internal volume 1.2 L
Mass 6.16 kg
Nominal opening 600 × 350 mm
Frame dimensions 660 × 390 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 600 mm
Nominal height B 350 mm
Frame width K 660 mm
Frame height E 390 mm
Casing depth C 150 mm
Connection-to-frame span L 775 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics A matching performance table for this variant is not available. Request selection for your duty.
Nominal opening 700 × 400 mm
Frame dimensions 750 × 440 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 700 mm
Nominal height B 400 mm
Frame width K 750 mm
Frame height E 440 mm
Casing depth C 150 mm
Connection-to-frame span L 875 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Row count 2
Fin spacing 2.5 mm
Connection designation G1
Circuit count 8
Heat exchange area 9 m²
Airflow 3000 m³/h
Hydraulic pressure drop 13.5 kPa
Heating capacity 65 kW
Internal volume 1.58 L
Mass 7.84 kg
Nominal opening 700 × 400 mm
Frame dimensions 750 × 440 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 700 mm
Nominal height B 400 mm
Frame width K 750 mm
Frame height E 440 mm
Casing depth C 150 mm
Connection-to-frame span L 875 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics A matching performance table for this variant is not available. Request selection for your duty.
Nominal opening 800 × 500 mm
Frame dimensions 860 × 540 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 800 mm
Nominal height B 500 mm
Frame width K 860 mm
Frame height E 540 mm
Casing depth C 150 mm
Connection-to-frame span L 975 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Row count 2
Fin spacing 2.5 mm
Connection designation G1
Circuit count 10
Heat exchange area 12.8 m²
Airflow 4300 m³/h
Hydraulic pressure drop 19.1 kPa
Heating capacity 94 kW
Internal volume 2.25 L
Mass 10.9 kg
Nominal opening 800 × 500 mm
Frame dimensions 860 × 540 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 800 mm
Nominal height B 500 mm
Frame width K 860 mm
Frame height E 540 mm
Casing depth C 150 mm
Connection-to-frame span L 975 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics A matching performance table for this variant is not available. Request selection for your duty.
Nominal opening 900 × 500 mm
Frame dimensions 960 × 540 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 900 mm
Nominal height B 500 mm
Frame width K 960 mm
Frame height E 540 mm
Casing depth C 150 mm
Connection-to-frame span L 1075 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Row count 2
Fin spacing 2.5 mm
Connection designation G1
Circuit count 10
Heat exchange area 14.4 m²
Airflow 4800 m³/h
Hydraulic pressure drop 25.6 kPa
Heating capacity 106 kW
Internal volume 2.51 L
Mass 11.8 kg
Nominal opening 900 × 500 mm
Frame dimensions 960 × 540 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 900 mm
Nominal height B 500 mm
Frame width K 960 mm
Frame height E 540 mm
Casing depth C 150 mm
Connection-to-frame span L 1075 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics A matching performance table for this variant is not available. Request selection for your duty.
Nominal opening 1000 × 500 mm
Frame dimensions 1060 × 540 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 1000 mm
Nominal height B 500 mm
Frame width K 1060 mm
Frame height E 540 mm
Casing depth C 150 mm
Connection-to-frame span L 1175 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics Archived catalogue values. Operating conditions are not shown; confirm performance for the selected duty.
Row count 2
Fin spacing 2.5 mm
Connection designation G1
Circuit count 10
Heat exchange area 16 m²
Airflow 5350 m³/h
Hydraulic pressure drop 30.8 kPa
Heating capacity 112 kW
Internal volume 2.78 L
Mass 12.8 kg
Nominal opening 1000 × 500 mm
Frame dimensions 1060 × 540 mm
Casing depth 150 mm
All drawing dimensions
Nominal width A 1000 mm
Nominal height B 500 mm
Frame width K 1060 mm
Frame height E 540 mm
Casing depth C 150 mm
Connection-to-frame span L 1175 mm Nominal opening, frame dimensions and casing depth are separate. They do not establish the complete envelope including connections.
Archived catalogue characteristics A matching performance table for this variant is not available. Request selection for your duty.
Recovered product description The previous site describes a 1000 × 500 variant-3 heater as a glycol unit and states 6900 m³/h, 119 kW and 82 Pa. The operating conditions and mixture are not specified, so these are historical figures, not a current selection.
Choose the function, fluid and fit A size is one part of selection. These three checks link the catalogue to the right application and replacement requirements.
1. Heating or cooling Choose the heat-transfer task first. A refrigerant cooling coil and an air-cooled condenser perform different duties and need separate selection.
2. Water, glycol or refrigerant State the fluid, temperatures and flow. For glycol, add its type and concentration; for a refrigerant, its designation and evaporating or condensing conditions.
3. Installation and connections Compare the opening, frame, depth, mounting holes and pipe positions. Define connection handedness relative to airflow; a perspective render cannot establish it.
Water, glycol or refrigerant? The fluid is a selection input, not a size. Specify water or the type and concentration of glycol; for a refrigerant coil, specify the refrigerant and operating conditions. A matching duct opening alone does not establish a suitable replacement.
Dimensions are taken from archive drawings and, where available, matching catalogue tables. Final supply requires an agreed drawing; the illustrations are not manufacturing documents. Frame and casing dimensions exclude some projecting parts. Confirm the full envelope, mounting holes and connections against your installation.
Questions about standard coil sizes Does a matching nominal size guarantee a replacement? No. Check the complete envelope, mounting, connections, airflow direction and required operating performance. The size label identifies the nominal opening, not every installation interface.
Do variants 2 and 3 have the same performance? Do not transfer a rating between variants. Matching performance-table rows are available for variant 2; variant 3 has drawings, but lacks its own table. A separate historical product description is identified in the relevant card.
What if none of the nine openings fits? Use the made-to-size or replacement route. Provide a drawing or measured dimensions and the operating duty; the series catalogue is not a limit on possible project specifications.